Explanation — How the Modbus adapter works, and why

This page is the mental model. For exact options see reference/; for tasks, the how-to guides.

The adapter is a consumer of the cross-language southbound contract (the same one the OPC UA reference adapter implements): it publishes a normalized SouthboundSignalUpdate envelope, exposes a read/write command surface, and emits southbound_health plus Modbus operational metrics. The cloud sees the same shape regardless of protocol — only device.adapter, the opaque signal.address, and the protocol-specific metric families differ. This adapter is the poll-based reference; OPC UA is the subscribe-based one.

Addressing follows the UNS: every topic is ecv1/{device}/{component}/{instance}/{class}[/channel], built and validated by the library — never a hand-assembled string. Telemetry rides the data class (ecv1/{device}/modbus-adapter/{instance}/data/{signal}); discrete events ride evt; the on-demand command surface rides the library’s cmd inbox; and the library owns state (a keepalive — whose RUNNING body also carries each configured slave’s live connectivity and state in an instances[] array), metric (southbound_health, system metrics, and Modbus operational metrics), and cfg automatically. Every message carries a top-level identity element ({hier, path, component, instance}) placing the reading in the enterprise tree — routing and partitioning never parse the body or the topic. A fleet consumer needs one wildcard per class (ecv1/+/+/+/data/#, …/evt/#, …/metric/#, …/state), not per-adapter topic templates.

Modbus has no eventing — a device only answers requests. So instead of subscribing, the adapter polls: each poll group has its own interval and its own worker thread that reads its signals, decides what changed, and publishes. “Change” is decided client-side: with publishMode: onChange (the default) a signal publishes only when its value moves past its deadband; with always it publishes every poll. This is the Modbus equivalent of OPC UA’s server-side monitored-item deadband — moved into the adapter because the protocol can’t do it for you.

Reading each signal with its own request would be slow. The poller coalesces signals of the same table into the fewest Modbus reads: it sorts by address, merges runs (bridging gaps up to maxGap), caps each block at the protocol limit (125 registers, 2000 bits), issues one read per block, and slices each signal’s value out. So 20 nearby holding registers become one FC3 instead of 20. Wall-clock per poll is the number of blocks, not the number of signals.

The type & scaling layer — the heart of it

Section titled “The type & scaling layer — the heart of it”

This is where Modbus differs most from a “typed” protocol like OPC UA. The wire only has bits and 16-bit registers; types are a fiction the adapter maintains from config. A float32 is two registers reassembled per the configured byte and word order and unpacked; a scaled int16 is one register times scale plus offset; a bool may be a coil or a single bit of a register. The codec (codec.py) is the one place that converts both ways and is exhaustively unit-tested across every type and all four order combinations.

Two consequences worth internalizing:

  • You must know the device’s register map and encoding — there is no discovery to fall back on. The map lives entirely in your config; get the address, type, and byte/word order right and the values are correct, get them wrong and you get plausible garbage.
  • Identity is explicit. signal.name is your label, signal.id (u<unit>/<table>/<addr>/<type>) is a stable canonical key, and signal.address is the protocol-native handle for round-tripping reads/writes.
  • Data plane — high-rate, fire-and-forget telemetry: SouthboundSignalUpdate out on the data class (through the library’s data() facade); discrete events out on the evt class (through events()) — a critical connection alarm (evt/critical/connection, raised on drop / cleared on restore) and an info/warning write audit (evt/{info|warning}/write). Severity derives the channel, so the topic and the body can never disagree.
  • Control plane — low-rate request/reply through the cmd inbox: sb/write, on-demand sb/read, and sb/status / sb/signals / reconnect / repoll verbs.

Keeping them separate means a consumer can fire a control verb without perturbing the telemetry stream, and routing/partitioning can key on the data-plane topic alone. The command inbox subscribes both command scopes (ecv1/{device}/modbus-adapter/cmd/# and ecv1/{device}/modbus-adapter/+/cmd/#). Every verb the adapter serves declares the instance scope: an instance-scoped topic addresses that device by its token, a component-scoped request names the device with an instance field in the request body, a disagreement between the two is refused with BAD_ARGS, and naming no instance at all addresses the sole configured device.

Metrics deliberately stay low-cardinality. southbound_health answers the common binary question (connectionState, interval readErrors), while the richer groups describe connection attempts, configured inventory, poll/read-block behavior, publish volume, and command activity. Their dimensions are bounded values like instance, pollGroup, table, publishMode, verb, and result; individual register addresses, signal names, endpoint URLs, and raw errors belong in data/events/logs, not in CloudWatch dimensions.

Every sample carries a normalized quality (GOOD/BAD/UNCERTAIN) plus qualityRaw (the native detail). This is structural, not adapter discipline: the library’s data() facade requires a quality on every sample it constructs, defaulting an omitted one to GOOD (Modbus has no native quality codes to report) and marking the synthesis qualityRaw: "unspecified" so a consumer can tell a synthesized GOOD from a device-reported one. A Modbus exception or timeout publishes BAD for every signal in the failed read block, with the exception text in qualityRaw, so a consumer sees an outage rather than a stale value silently persisting. (A block failure has no value at all to report — not even a “null” reading — so that one case goes through the facade’s raw escape hatch rather than its normal value-required builder; see publisher.py’s module docstring.)

One adapter process runs one worker per component.instances[] entry. Each connects (and reconnects, retrying every 5s) on its own thread, so a device going offline only takes its own instance’s signals to BAD — the others keep streaming. This is the fault-isolation you want when one adapter fronts a fleet.

Each slave’s up/down state is surfaced per-instance in the main state keepalive’s instances[] array ({instance, connected, detail}, one entry per configured slave) — the component keeps a single UNS identity under main and reports each connection’s health there, rather than minting a separate UNS instance per slave. That connected flag is live liveness: it is driven by the poll reads themselves — any response that arrives (data, or even a slave exception for e.g. an illegal address) marks the link up, while a transport/IO error, a ModbusIOException, or no response marks it down — not pymodbus’s cached client.connected, which reflects intent and lags a socket that died mid-session. So a southbound death partway through a session is reflected promptly as connected: false on the next keepalive instead of a stale “connected”.

Classic Modbus has no authentication or encryption — it’s plaintext on the wire. There is deliberately no credential/cert handling in this adapter; secure Modbus at the network layer (a dedicated VLAN, a VPN, firewalling the device subnet). (Modbus/TLS exists in the spec but is rarely supported by devices; it’s out of scope here.) This is the clean simplification versus the OPC UA adapter, whose security layer does not carry over.