Recipes for specific tasks. Each assumes the adapter builds and runs (see the tutorial). For concepts see explanation.md; for exhaustive options see reference/.
Define a register map (signals)
Section titled “Define a register map (signals)”Modbus has no discovery — you declare every signal. Put signals in a poll group on the instance:
"pollGroups": [ { "id": "process", "pollIntervalMs": 500, "signals": [ { "name": "Temperature", "table": "holding", "address": 0, "type": "float32", "scale": 0.1 }, { "name": "Running", "table": "coil", "address": 0, "type": "bool" }, { "name": "FaultBit2", "table": "holding", "address": 10, "type": "bool", "bit": 2 } ] }]table:holding/input(16-bit registers) orcoil/discrete(bits).addressis the 0-based PDU address (not the 4xxxx/1-based convention).- Pick
typeto match the device’s encoding; setwordOrder/byteOrderif it isn’t big/big (see data-types). Usescale/offsetfor engineering units,bitto pull one bit of a register.
Match the device’s number format
Section titled “Match the device’s number format”If 32/64-bit values come out wrong (byte-swapped or word-swapped), set the order on the signal:
{ "name": "Energy", "table": "holding", "address": 20, "type": "uint32", "wordOrder": "little" }The four combinations of wordOrder × byteOrder cover ABCD/BADC/CDAB/DCBA. The
data-types table maps them out.
Tune poll rate and reduce traffic
Section titled “Tune poll rate and reduce traffic”| You want… | Set |
|---|---|
| Faster/slower polling | pollGroups[].pollIntervalMs |
| Publish only on real change | publishMode: "onChange" (default) + a deadband per signal |
| Publish every poll | publishMode: "always" |
| Drop sensor jitter | deadband: { "type": "absolute", "value": 0.5 } (or percent) |
| Fewer, larger messages | publish.batchMs > 0 (coalesce a signal’s samples per interval) |
| Fewer Modbus reads | raise maxGap so nearby signals merge into one read block |
The poller already merges contiguous signals of the same table into single reads (capped at 125
registers / 2000 bits); maxGap lets it bridge small holes between signals.
Read and write signals from a client
Section titled “Read and write signals from a client”Both go through the library command inbox (ecv1/{device}/modbus-adapter[/{instance}]/cmd/{verb}).
Set header.name to the verb and header.reply_to + header.correlation_id for the reply. Select
the device either by putting its instance token in the topic or with instance in the body on the
component-scope topic (optional with one device); naming both, differently, is refused with
BAD_ARGS. The reply is { "ok": true, "result": … }.
Write (the target signal.id must be on the instance’s writes.allow list — e.g.
"writes": { "allow": [ "u1/holding/6/float32" ] }):
publish ecv1/<device>/modbus-adapter/cmd/sb/write { "header": { "name": "sb/write", "reply_to": "app/r", "correlation_id": "7" }, "body": { "instance": "plc1", "writes": [ { "name": "Setpoint", "value": 42.5 } ] } }subscribe app/r → { "ok": true, "result": { "written": 1, "results": [ … ] } }Read — request/reply:
publish ecv1/<device>/modbus-adapter/cmd/sb/read { "header": { "name": "sb/read", "reply_to": "app/r", "correlation_id": "8" }, "body": { "instance": "plc1", "signals": [ { "name": "Temperature" } ] } }subscribe app/r → { "ok": true, "result": { "id": "plc1", "reads": [ … ] } }Address a signal by name (a configured signal) or explicitly by
{ unitId?, table, address, type, wordOrder?, scale?, … } for arbitrary access. Read-only tables
(discrete/input) are reported per-entry as ok:false. Each write also emits an
evt/info/write/evt/warning/write audit event. Full schemas:
messaging reference.
Bridge several devices from one adapter
Section titled “Bridge several devices from one adapter”Add an instance per device under component.instances[] — each gets its own connection/worker, so one
device being down doesn’t disturb the others:
"instances": [ { "id": "plc1", "connection": { "transport": "tcp", "host": "10.0.0.50", "port": 502, "unitId": 1 }, "pollGroups": [ ... ] }, { "id": "plc2", "connection": { "transport": "tcp", "host": "10.0.0.51", "port": 502, "unitId": 1 }, "pollGroups": [ ... ] }]Multiple unit ids behind one gateway: give each poll group its own unitId within a single
instance.
Use serial RTU
Section titled “Use serial RTU”"connection": { "transport": "rtu", "serialPort": "/dev/ttyUSB0", "baudRate": 9600, "parity": "N", "stopBits": 1, "byteSize": 8, "unitId": 1 }For a serial-to-Ethernet gateway that speaks RTU framing over a socket, use
"transport": "rtutcp" with host/port. The signal/type/poll model is identical across transports.
Deploy to a platform
Section titled “Deploy to a platform”HOST: python main.py --platform HOST --transport MQTT ./messaging.json -c FILE ./config.json -t my-thing
Greengrass: package per gdk-config.json/recipe.yaml; config comes from the deployment
(--platform GREENGRASS -c GG_CONFIG).
Kubernetes: build the image and apply the manifests (config from a mounted ConfigMap, identity from the Downward API).
Observe health and status
Section titled “Observe health and status”- Metric
southbound_health(connectionState,readErrors) — withmetricEmission.target: messagingit auto-publishes on the UNSmetricclass (ecv1/{device}/modbus-adapter/metric/southbound_health);log/cloudwatch/prometheusalso work. - Operational metrics
ModbusConnection,ModbusInventory,ModbusPoll,ModbusPublish, andModbusCommand— low-cardinality metric families intended for CloudWatch/Prometheus dashboards. Their dimensions use instance, connection type, poll group, table, publish mode, command verb, and result only; signal names, addresses, endpoint URLs, and error text are not dimensions. UseModbusPollfor poll health (pollCycles,protocolReadErrors,samplesBad,pollOverruns),ModbusPublishfor data-plane output (dataMessagesPublished,samplesPublished,publishFailures),ModbusConnectionfor link state and reconnect pressure, andModbusCommandfor control-plane request volume, latency, and errors. - State keepalive: the library publishes
ecv1/{device}/modbus-adapter/stateevery ~5 s; the RUNNING keepalive also carries aninstances[]array ({instance, connected, state, detail}) — each configured slave’s live up/down flag, its state token (ONLINE/PAUSED/BACKOFF/CONNECTING), and its endpoint. - Events:
evt/critical/connection(link up/down per instance, a stateful alarm — raised on drop, cleared on restore) andevt/{info|warning}/write(write audit) on theevtclass; severity derives the channel. - Status verb:
sb/status→{ state, connected, paused, metrics }— the same state token the keepalive publishes. Signals verb:sb/signals→ the resolved signal list with addresses. - Logs: each subsystem logs under its own name with the
[<instanceId>]prefix.