Modbus carries only bits (coils, discrete inputs) and 16-bit registers (holding, input). This adapter synthesizes richer types from those primitives. Every signal declares its type (and, for multi-register types, byte/word order); the adapter assembles registers into the value on read and splits the value back into registers on write. All conversion is in modbus_adapter/codec.py.

Table FC (read) Access Element
coil 1 read/write 1 bit → bool
discrete 2 read-only 1 bit → bool
holding 3 read/write 16-bit register
input 4 read-only 16-bit register
type Registers On-wire JSON (read) Write input Notes
bool 1 bit, or 1 register + bit boolean boolean coil/discrete; or a single bit of a holding/input register via bit
int16 1 number number (int) signed
uint16 1 number number (int)
int32 2 number number (int)
uint32 2 number number (int)
int64 4 number number (int)
uint64 4 number number (int)
float32 2 number number IEEE-754 single
float64 4 number number IEEE-754 double
string count string string UTF-8, null-padded; count registers (2 chars each)

A register is 16 bits (2 bytes). A 32/64-bit value spans 2–4 registers; devices differ in how the bytes are laid out. Two independent knobs cover the four real-world layouts:

  • wordOrderbig (default): most-significant register first; little: registers reversed (word swap).
  • byteOrderbig (default): high byte first within each register; little: bytes swapped.
wordOrder / byteOrder Layout (32-bit ABCD)
big / big ABCD
big / little BADC
little / big CDAB
little / little DCBA
  • scale / offset (numeric types): read value = raw·scale + offset; write inverts it (raw = round((value − offset) / scale) for integer types). With no scale/offset an integer type stays an integer on the wire; with a scale it becomes a float.
  • bit (0–15, holding/input + type: bool): publishes a single bit of a register as a boolean. Bit writes (read-modify-write) are not supported and are skipped with a warning.

Each SouthboundSignalUpdate / read result carries:

  • signal.name — the configured signal name (also the sanitized data-class channel token).
  • signal.id — a stable canonical id, u<unitId>/<table>/<address>/<type> (e.g. u1/holding/24/float32).
  • signal.address — the protocol-native handle: { unitId, table, address, type, wordOrder?, byteOrder?, bit?, count? }.
  • Integers use the full 64-bit range; consumers whose JSON parser uses IEEE-754 doubles (e.g. JavaScript) may lose precision above 2^53.
  • bool is a JSON boolean; string a JSON string; everything else a JSON number.
  • Modbus has no device-side timestamp, so sourceTs is null and serverTs is the adapter’s read time.