Sample Configurations

Complete, copy-paste-ready configurations for the Modbus adapter (com.mbreissi.edgecommons.ModbusAdapter), built up from a trivial dev loop to a realistic, multi-table device map placed in the Unified Namespace, plus how data reaches the cloud — with an explanation of what every option does and how it changes runtime behavior.

These are worked examples. For the exhaustive option list see reference/configuration.md; for the type/byte-order system see reference/data-types.md; for task recipes see how-to-guides.md; for the message envelopes see reference/messaging-interface.md; for the data/control plane model see explanation.md.

The adapter loads one JSON document from -c/--config. The top level may contain component (required — the adapter) and the standard edgecommons sections tags, hierarchy, identity, topic, messaging, metricEmission, logging, heartbeat, and (opt-in) streaming. Timing values resolve signal/group ▸ instance defaultsglobal.defaults ▸ built-in.

All topics follow the Unified Namespace: ecv1/{device}/{component}/{instance}/{class}[/channel], built and validated by the library from the hierarchy/identity config (there are no per-instance or per-signal topic templates). Telemetry rides the data class, events evt, the command surface the cmd inbox; the library owns state/metric/cfg automatically.


Every register table maps to a Modbus function code, and the adapter always uses the 0-based PDU addressnot the 1-based 4xxxx/3xxxx/1xxxx/0xxxx convention printed in most vendor manuals. The two relate by a fixed offset per table:

Table table value FC (read) FC (write) Element Vendor convention address (config)
Coil coil 1 5 / 15 1 bit → bool 0xxxx (00001…) vendor − 1
Discrete input discrete 2 — (read-only) 1 bit → bool 1xxxx (10001…) vendor − 10001
Holding register holding 3 6 / 16 16-bit register 4xxxx (40001…) vendor − 40001
Input register input 4 — (read-only) 16-bit register 3xxxx (30001…) vendor − 30001

So holding register 40001 is address: 0, 40003 is address: 2, and so on — multi-register values (a float32/uint32 spans 2 registers) advance the vendor number by 2 each. The tables below list both columns so you can transcribe a vendor map without arithmetic mistakes.


1. Minimal local / dev (HOST + MQTT, Modbus TCP)

Section titled “1. Minimal local / dev (HOST + MQTT, Modbus TCP)”

The smallest config that polls a Modbus TCP slave/simulator and republishes to a local MQTT broker. Pair it with the local broker (docker compose -f test-infra/compose.yaml up -d) and a TCP simulator (e.g. the bundled validation/modbus_sim_server.py on :5020).

Run it:

Terminal window
python main.py --platform HOST --transport MQTT ./messaging.json -c FILE ./config.json -t dev-thing

config.json:

{
"logging": { "level": "INFO" },
"messaging": {
"local": { "type": "mqtt", "host": "localhost", "port": 1883, "clientId": "modbus-adapter" }
},
"component": {
"instances": [
{
"id": "plc1",
"connection": { "transport": "tcp", "host": "127.0.0.1", "port": 5020, "unitId": 1 },
"pollGroups": [
{ "id": "main", "pollIntervalMs": 1000,
"signals": [
{ "name": "Counter16", "table": "holding", "address": 0, "type": "uint16" },
{ "name": "Running", "table": "coil", "address": 0, "type": "bool" }
] }
]
}
]
}
}

You can drop the messaging section entirely and pass the broker inline instead: --transport MQTT ./messaging.json, where messaging.json holds the same { "messaging": { "local": … } }.

What each option does at runtime

Option Effect
logging.level Standard edgecommons log level. INFO logs connect/poll-group summaries and errors; DEBUG adds per-call detail.
messaging.local.type/host/port The transport target for published SouthboundSignalUpdate messages. On HOST this is the local MQTT broker the adapter connects to (and the same broker your consumers subscribe on).
messaging.local.clientId MQTT client id used for the broker session. Make it unique per process so two adapters don’t fight over the same session.
instances[].id Stable instance id. The {instance} token of the data/evt topics, device.instance in every message, and the [plc1] prefix in logs.
connection.transport: tcp Opens a Modbus/TCP socket to host:port.
connection.host / port The device endpoint. Default 127.0.0.1:502.
connection.unitId Default Modbus unit/slave id used for reads/writes unless a poll group or signal-ref overrides it.
pollGroups[].pollIntervalMs How often this group is read end-to-end. 1000 = once per second. Lower = fresher data but more bus traffic.
signal name Required human name; the sanitized data-class channel token and the friendly handle for reads/writes.
signal table Which Modbus space + function code: holding(FC3) / input(FC4) registers, coil(FC1) / discrete(FC2) bits.
signal address 0-based PDU address (see the convention table above).
signal type How raw registers/bits decode. Register tables default to uint16; bit tables are always bool.

With publishMode unset it defaults to onChange and (no deadband) republishes whenever a value differs from the last published one. With no messaging connection the adapter still polls but cannot publish.


This is the centerpiece. A single instance talks to a pump skid behind one TCP gateway at 10.0.0.50:502, addressing two unit ids on the same socket: the skid PLC (unitId 1, control/status/alarms) and an integrated power/energy meter (unitId 2, totalizers/diagnostics). The map below is representative of a real device — contiguous ranged blocks, mixed data types, a word-swapped energy counter, a byte-swapped float, and a packed status word with bit-extracted alarms.

Holding registers — unitId 1, FC3 read / FC6·FC16 write (process values, setpoints, status word)

Vendor address Signal type scale R/W Engineering meaning
40001–40002 0 Temperature float32 R Process temperature °C
40003–40004 2 Pressure float32 R Header pressure bar
40005–40006 4 FlowRate float32 R Flow m³/h
40007–40008 6 Setpoint float32 R/W Temperature setpoint °C
40009 8 PumpSpeedCmd uint16 0.1 R/W Pump speed command % (0.1 resolution)
40010 9 TempTrim int16 0.1 R/W Signed trim °C (can be negative)
40017 16 StatusWord uint16 R Packed status/alarm bits (see below)

Input registers — unitId 2, FC4 read-only (meter totalizers and diagnostics)

Vendor address Signal type order / scale Engineering meaning
30001–30002 0 EnergyImport uint32 wordOrder: little, scale: 0.001 Imported energy kWh (low word first)
30003–30004 2 EnergyExport uint32 wordOrder: little, scale: 0.001 Exported energy kWh
30005–30006 4 NetPower int32 scale: 0.001 Signed net power kW (− = export)
30007–30008 6 RunHours uint32 Run-time hours
30009 8 FaultCount uint16 Lifetime fault count
30011–30018 10 SerialNo string count: 8 Meter serial (16 UTF-8 bytes)
30019 18 FirmwareVer uint16 Firmware revision
30021–30022 20 PhaseAngle float32 byteOrder: little Phase angle ° (byte-swapped device)

Coils — unitId 1, FC1 read / FC5·FC15 write (command bits, polled for read-back)

Vendor address Signal Meaning
00001 0 RunCmd Start/stop command
00002 1 ResetCmd Fault reset
00003 2 RemoteEnable Remote-control enable

Discrete inputs — unitId 1, FC2 read-only (status bits)

Vendor address Signal Meaning
10001 0 Running Pump running
10002 1 Fault Fault active
10003 2 LocalMode Local (not remote)
10004 3 HighLevelSwitch High-level float
10005 4 LowLevelSwitch Low-level float
10006 5 DoorOpen Enclosure door

Status word bit extraction — StatusWord (holding address 16, unitId 1)

A single 16-bit register packs six status flags. Each is surfaced as its own boolean signal with type: bool + bit: N on the same address 16, so all six come from one register read:

bit Signal Meaning
0 AlarmHigh High-process alarm
1 AlarmLow Low-process alarm
2 OverTemp Over-temperature
3 MotorFault Motor fault
4 CommError Field-bus comm error
5 MaintenanceDue Maintenance due
{
"tags": { "site": "plant1", "area": "pumphouse", "line": "5" },
"hierarchy": { "levels": ["site", "area", "line", "device"] },
"identity": { "site": "plant1", "area": "pumphouse", "line": "5" },
"logging": { "level": "INFO" },
"messaging": {
"local": { "type": "mqtt", "host": "localhost", "port": 1883, "clientId": "modbus-skid1" }
},
"metricEmission": { "target": "messaging" },
"component": {
"global": { "defaults": { "pollIntervalMs": 1000, "publishMode": "onChange", "maxGap": 8, "batchMs": 0 } },
"instances": [
{
"id": "skid1",
"connection": { "transport": "tcp", "host": "10.0.0.50", "port": 502, "unitId": 1, "timeoutMs": 1000 },
"publish": { "batchMs": 0 },
"writes": { "allow": [ "u1/holding/6/float32", "u1/holding/8/uint16", "u1/coil/0/bool", "u1/coil/1/bool", "u1/coil/2/bool" ] },
"pollGroups": [
{ "id": "process", "pollIntervalMs": 250, "unitId": 1, "publishMode": "onChange", "maxGap": 8,
"signals": [
{ "name": "Temperature", "table": "holding", "address": 0, "type": "float32",
"deadband": { "type": "absolute", "value": 0.2 } },
{ "name": "Pressure", "table": "holding", "address": 2, "type": "float32",
"deadband": { "type": "percent", "value": 1.0 } },
{ "name": "FlowRate", "table": "holding", "address": 4, "type": "float32" },
{ "name": "Setpoint", "table": "holding", "address": 6, "type": "float32" },
{ "name": "PumpSpeedCmd", "table": "holding", "address": 8, "type": "uint16", "scale": 0.1 },
{ "name": "TempTrim", "table": "holding", "address": 9, "type": "int16", "scale": 0.1 },
{ "name": "AlarmHigh", "table": "holding", "address": 16, "type": "bool", "bit": 0 },
{ "name": "AlarmLow", "table": "holding", "address": 16, "type": "bool", "bit": 1 },
{ "name": "OverTemp", "table": "holding", "address": 16, "type": "bool", "bit": 2 },
{ "name": "MotorFault", "table": "holding", "address": 16, "type": "bool", "bit": 3 },
{ "name": "CommError", "table": "holding", "address": 16, "type": "bool", "bit": 4 },
{ "name": "MaintenanceDue", "table": "holding", "address": 16, "type": "bool", "bit": 5 }
] },
{ "id": "totals", "pollIntervalMs": 5000, "unitId": 2, "publishMode": "always", "maxGap": 8,
"signals": [
{ "name": "EnergyImport", "table": "input", "address": 0, "type": "uint32", "wordOrder": "little", "scale": 0.001 },
{ "name": "EnergyExport", "table": "input", "address": 2, "type": "uint32", "wordOrder": "little", "scale": 0.001 },
{ "name": "NetPower", "table": "input", "address": 4, "type": "int32", "scale": 0.001 },
{ "name": "RunHours", "table": "input", "address": 6, "type": "uint32" },
{ "name": "FaultCount", "table": "input", "address": 8, "type": "uint16" },
{ "name": "SerialNo", "table": "input", "address": 10, "type": "string", "count": 8 },
{ "name": "FirmwareVer", "table": "input", "address": 18, "type": "uint16" },
{ "name": "PhaseAngle", "table": "input", "address": 20, "type": "float32", "byteOrder": "little" }
] },
{ "id": "status", "pollIntervalMs": 1000, "unitId": 1, "publishMode": "onChange",
"signals": [
{ "name": "RunCmd", "table": "coil", "address": 0, "type": "bool" },
{ "name": "ResetCmd", "table": "coil", "address": 1, "type": "bool" },
{ "name": "RemoteEnable", "table": "coil", "address": 2, "type": "bool" },
{ "name": "Running", "table": "discrete", "address": 0, "type": "bool" },
{ "name": "Fault", "table": "discrete", "address": 1, "type": "bool" },
{ "name": "LocalMode", "table": "discrete", "address": 2, "type": "bool" },
{ "name": "HighLevelSwitch", "table": "discrete", "address": 3, "type": "bool" },
{ "name": "LowLevelSwitch", "table": "discrete", "address": 4, "type": "bool" },
{ "name": "DoorOpen", "table": "discrete", "address": 5, "type": "bool" }
] }
]
}
]
}
}

Each poll group runs on its own daemon thread, so the 250 ms process loop, the 5000 ms totals loop, and the 1000 ms status loop run concurrently and independently. The poller coalesces each group’s signals per table into the fewest Modbus reads, sorting by address and bridging gaps up to maxGap.

process (fast control data, unitId 1, every 250 ms). All twelve signals are holding registers, so they coalesce into one read. The numeric signals occupy registers 0–9 (contiguous), and the six alarm bits all read register 16. With maxGap 8 the poller bridges the 6-register gap (registers 10–15 are read but unused) and issues a single read_holding_registers(0, count=17):

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
└Temperature┘└Pressure┘└FlowRate┘└Setpnt┘Pump Trim └── unused (gap) ──┘ Status
  • Temperature decodes a float32, and only republishes when it moves at least 0.2 °C from the last published value (deadband absolute).
  • Pressure republishes only when it changes by at least 1.0 percent of the previous value (deadband percent). When the previous value is 0, percent can’t be computed so any change publishes.
  • FlowRate has no deadband, so under onChange it republishes on any change.
  • PumpSpeedCmd/TempTrim are writable; reading them here gives a command read-back. TempTrim is int16, so it carries negative trims correctly. Both apply scale 0.1, so raw 45545.5.
  • AlarmHigh…MaintenanceDue extract bits 0–5 of the one StatusWord register, surfacing packed bits as individual booleans (each on its own data channel, e.g. .../data/AlarmHigh).
  • Had maxGap been < 6 (e.g. the contiguous-only maxGap: 0), the StatusWord block would not merge and the group would issue two reads — read_holding_registers(0, count=10) and read_holding_registers(16, count=1).

totals (slow meter counters, unitId 2, every 5 s, always). unitId: 2 overrides the connection’s unitId: 1, addressing the meter behind the same socket. publishMode: always republishes every poll regardless of change — right for monotonic counters and a steady “still alive” signal. All eight signals are input registers spanning 0–21; the two 1-register gaps (9, 19) are ≤ maxGap 8, so they coalesce into a single read_input_registers(0, count=22).

  • EnergyImport/EnergyExport are uint32 with wordOrder: little because this meter stores the low-order register first; without it the value is word-swapped and wildly wrong. scale 0.001 converts Wh counts to kWh (a scaled integer is emitted as a float).
  • NetPower is int32 so it can go negative when the site exports.
  • SerialNo is a string spanning count: 8 registers (16 UTF-8 bytes, null-trimmed).
  • PhaseAngle is a float32 with byteOrder: little (a BADC device): the bytes within each register are swapped while the register order stays big — see the four-layout table in reference/data-types.md.

status (command read-back + status bits, unitId 1, every 1 s). Coils and discretes are different tables, so coalescing produces one read each: read_coils(0, count=3) and read_discrete_inputs(0, count=6). Single bits decode straight to booleans.

Net bus loadprocess 1 read × 4/s + status 2 reads × 1/s + totals 1 read × 0.2/s ≈ 6.2 requests/second across both unit ids on the one socket.

Every SouthboundSignalUpdate publishes on the UNS data class, ecv1/{device}/modbus-adapter/{instance}/data/{signal}, minted and validated by the library — the {signal} channel is the signal name passed through the UNS token sanitizer (/ + # \, control chars → _). With thing name gw-01, hierarchy.levels = [site, area, line, device], and instance skid1:

Signal (register) Resolved topic
Temperature (holding 0, u1) ecv1/gw-01/modbus-adapter/skid1/data/Temperature
EnergyImport (input 0, u2) ecv1/gw-01/modbus-adapter/skid1/data/EnergyImport
RunCmd (coil 0, u1) ecv1/gw-01/modbus-adapter/skid1/data/RunCmd
AlarmHigh (holding 16 bit 0, u1) ecv1/gw-01/modbus-adapter/skid1/data/AlarmHigh

The enterprise location rides the top-level identity element, not the topic: identity.path = "plant1/pumphouse/5/gw-01". A fleet consumer subscribes one wildcard ecv1/+/+/+/data/# rather than per-signal templates.

Worked example — AlarmHigh. It reads bit 0 of StatusWord on unitId 1; its topic is ecv1/gw-01/modbus-adapter/skid1/data/AlarmHigh, and the message carries the stamped identity plus the canonical signal identity in the body:

"identity": { "hier": [ {"level":"site","value":"plant1"}, {"level":"area","value":"pumphouse"},
{"level":"line","value":"5"}, {"level":"device","value":"gw-01"} ],
"path": "plant1/pumphouse/5/gw-01", "component": "modbus-adapter", "instance": "skid1" },
"body": {
"device": { "adapter": "modbus", "instance": "skid1", "endpoint": "tcp://10.0.0.50:502 unit=1" },
"signal": {
"id": "u1/holding/16/bool",
"name": "AlarmHigh",
"address": { "unitId": 1, "table": "holding", "address": 16, "type": "bool", "bit": 0 }
},
"samples": [ { "value": true, "quality": "GOOD", "qualityRaw": "unspecified", "serverTs": "2026-07-03T01:48:00Z" } ]
}

signal.id is the stable canonical id u<unitId>/<table>/<address>/<type>; signal.address is the protocol-native handle. Both are independent of the topic, so a consumer keys on identity regardless of addressing. This body is constructed by the library’s data() facade (not hand-assembled): quality has no Modbus-native meaning, so an omitted quality defaults to GOOD with the qualityRaw: "unspecified" marker; sourceTs is omitted (never synthesized) since Modbus has no device timestamp. To surface alarm transitions as discrete events (not just polled data), consume the adapter’s severity-segmented evt/critical/connection/evt/{info|warning}/write on ecv1/+/+/+/evt/#.

Option Effect on runtime behavior
global.defaults / instance defaults Fallback pollIntervalMs / publishMode / maxGap / batchMs inherited when a group/instance omits them. Resolution order is group ▸ instance defaultsglobal.defaults ▸ built-in.
connection.unitId Default unit id for the instance; overridden here per-group (totals → unit 2).
connection.timeoutMs Per-request response timeout (default 1000). A read that exceeds it marks that block’s signals BAD and increments readErrors.
publish.batchMs 0 = publish each sample immediately; >0 buffers per signal and flushes together (see batching). Set under publish or defaults; not per poll group.
writes.allow Array of stable signal.ids the sb/write verb may write, checked before any device I/O. Anything not listed is refused; a wholly-refused batch replies with a WRITE_NOT_ALLOWED error. Empty (the default) → the device is read-only.
hierarchy / identity Place the device in the UNS enterprise tree (envelope identity); the last hierarchy level is the resolved thing name = the topic {device}.
pollGroups[].pollIntervalMs One full read-decode-publish pass for the group. The loop subtracts its own work time, so a slow read shortens (never lengthens) the next sleep — the configured cadence is the ceiling.
pollGroups[].unitId Overrides connection.unitId for this group — addresses multiple slaves behind one TCP/RTU-TCP gateway or RTU line from one instance.
pollGroups[].publishMode: onChange A decoded value publishes only if it passes its deadband vs the last published value (the first read always publishes). Cuts message volume on steady signals.
pollGroups[].publishMode: always Every poll publishes, change or not. Use for counters/totalizers or a heartbeat-style feed.
pollGroups[].maxGap Largest address gap (registers/bits) the coalescer bridges to merge two signals into one read. 0 = strictly contiguous only; higher = fewer, larger reads (less overhead) at the cost of reading unused registers. Each block is capped at the protocol max (125 registers, 2000 bits). Coalescing is per table.
signal type (int16/uint16/int32/uint32/int64/uint64/float32/float64/string/bool) Determines how many registers the signal spans and how the raw words are interpreted (see data-types).
signal wordOrder Order of the registers in a multi-register value. big (default) = most-significant first; little = reversed (word swap).
signal byteOrder Order of bytes within each register. big (default)/little. The two knobs cover ABCD/BADC/CDAB/DCBA. Wrong order = right magnitude class, garbled value.
signal scale / offset Linear transform value = raw × scale + offset on read (inverted on write). Converts raw counts to engineering units; a scaled integer is emitted as a float.
signal count Registers a string spans (2 UTF-8 bytes each). Required for string.
signal bit (0–15) Publishes a single bit of a holding/input register as a boolean. Only valid with type: bool on a register table. Bit writes (read-modify-write) are not supported.
signal deadband Per-signal change filter under onChange: none (any change), absolute (`
signal name The sanitized data-class channel token (.../data/<name>) and the friendly write/read ref; signal.id/signal.address in the body are what consumers key on.

batchMs (under publish, or global/instance defaults) coalesces messages across time:

"publish": { "batchMs": 1000 }
  • batchMs: 0 (default) — every sample publishes immediately as its own SouthboundSignalUpdate.
  • batchMs > 0 — samples are buffered per signal and flushed together on a timer every batchMs, so one message can carry several samples for a signal. This trades freshness/latency for far fewer, larger messages — useful on constrained uplinks. The device’s flush tick is batchMs (or 5 s when batching is off); it also drives the periodic southbound_health emission.

3. Northbound: from the local bus to the cloud

Section titled “3. Northbound: from the local bus to the cloud”

Everything above publishes to the local bus — Greengrass IPC on the GREENGRASS platform, the local MQTT broker on HOST/KUBERNETES. That is the adapter’s data plane: SignalUpdatePublisher sends every SouthboundSignalUpdate on the UNS data class through the instance’s data() facade (which constructs the body and mints the topic), and the read/write/control surface is served by the library command inbox (ecv1/{device}/modbus-adapter/cmd/#) — both on the default provider channel (the local broker on HOST, IPC on Greengrass). On-box consumers read those topics.

What the adapter sends to the cloud itself. The one northbound path the adapter wires directly is its own operational telemetry — the heartbeat, southbound_health, and the Modbus operational metric families (ModbusConnection, ModbusInventory, ModbusPoll, ModbusPublish, ModbusCommand). The library can deliver them straight to AWS IoT Core alongside the local bus: on HOST/KUBERNETES the dual-MQTT provider holds the northbound mTLS session next to the local one. Opt in with messaging.northbound plus a heartbeat / metric target set to destination: "northbound":

{
"messaging": {
"local": { "type": "mqtt", "host": "localhost", "port": 1883, "clientId": "modbus-skid1" },
"northbound": {
"endpoint": "a1b2c3d4e5f6g7-ats.iot.us-east-1.amazonaws.com",
"port": 8883,
"clientId": "modbus-skid1",
"credentials": {
"certPath": "/greengrass/v2/thingCert.crt",
"keyPath": "/greengrass/v2/privKey.key",
"caPath": "/greengrass/v2/rootCA.pem"
}
}
},
// Heartbeat, health, and operational metrics go to IoT Core (low rate);
// register data stays on the local bus.
"heartbeat": {
"intervalSecs": 30,
"destination": "iotcore",
"measures": { "cpu": true, "memory": true }
},
"metricEmission": {
"target": "messaging",
"targetConfig": { "destination": "iotcore" }
}
}

The heartbeat keepalive rides the UNS state class and metrics ride the metric class automatically — destination: "northbound" routes those reserved-class publishes to IoT Core instead of the local broker.

On GREENGRASS the same destination: "northbound" routes through the Nucleus’ IoT Core connection, so messaging.northbound is not needed there.

Forwarding the register data itself. The adapter does not push polled register telemetry off-box — it publishes locally and stops there. Getting that data to the cloud is a deployment choice, handled by a separate consumer of the local topics:

  • Low-rate, actionable items (state, alarms, a setpoint readback someone acts on) — re-publish to AWS IoT Core via a Greengrass/IoT-Core topic bridge (rules engine) or a small on-box subscriber. IoT Core is priced per message, so keep this sparse.
  • High-rate, high-volume process data for analytics or a historian — the library’s streaming subsystem, gg.streams(), which batches and compresses into a durable on-disk buffer that drains to Kinesis or Kafka and survives WAN outages. See the Streaming guide and the streaming reference for its configuration; it is a edgecommons subsystem you run in a forwarding component, not a modbus-adapter option.

The adapter supports three transports — tcp, rtu (serial line), and rtutcp (RTU framing over a TCP socket, for serial-to-Ethernet gateways). The signal/type/poll model is identical across all three; only the connection block changes.

Serial RTU (/dev/ttyUSB0, COM3, …):

{
"messaging": { "local": { "type": "mqtt", "host": "localhost", "port": 1883 } },
"component": {
"instances": [
{
"id": "meter1",
"connection": {
"transport": "rtu",
"serialPort": "/dev/ttyUSB0",
"baudRate": 19200, "parity": "E", "stopBits": 1, "byteSize": 8,
"unitId": 5, "timeoutMs": 1500
},
"pollGroups": [
{ "id": "energy", "pollIntervalMs": 2000,
"signals": [
{ "name": "Voltage", "table": "input", "address": 0, "type": "float32" },
{ "name": "Energy", "table": "input", "address": 12, "type": "uint32", "wordOrder": "little" }
] }
]
}
]
}
}

RTU-over-TCP (same RTU framing, reached through a gateway’s IP:port — swap only the connection):

"connection": { "transport": "rtutcp", "host": "10.0.0.200", "port": 502, "unitId": 5, "timeoutMs": 1500 }

What each option does at runtime

Option Effect
transport: rtu Builds a ModbusSerialClient with the RTU framer. host/port are ignored; serialPort is required.
transport: rtutcp Builds a ModbusTcpClient with the RTU framer over the socket — the right choice for a serial-to-Ethernet gateway that wraps raw RTU frames. Uses host/port, ignores serialPort.
serialPort OS serial device path/name (/dev/ttyUSB0, COM3). RTU only.
baudRate Line speed (default 9600). Must match the device exactly or every frame fails to decode.
parity N/E/O (default N). Must match the device.
stopBits 1 or 2 (default 1). Must match the device.
byteSize Bits per character (default 8).
unitId The RTU slave address on the bus. On a multidrop RTU line each device has a distinct id; set it per instance, or per poll group when several slaves share one line/gateway.
timeoutMs Per-request response timeout (default 1000). Serial lines are slow — raise it (e.g. 1500). A read that exceeds it marks the block’s signals BAD and increments readErrors.

Because a serial line is a single shared medium, only one request is in flight at a time and poll groups effectively serialize on it. Keep pollIntervalMs realistic for the baud rate and register count — over-aggressive polling on RTU just queues reads and inflates latency.


On Greengrass the config is the component’s ComponentConfig and messaging uses Greengrass IPC — no messaging section and no broker. The config below is the recipe.yaml DefaultConfiguration.ComponentConfig; override connection and pollGroups for your device at deploy time. The component runs main.py --platform GREENGRASS (config source defaults to GG_CONFIG, transport to IPC).

ComponentConfiguration:
DefaultConfiguration:
ComponentConfig:
logging:
level: "INFO"
python_format: "%(asctime)s [%(levelname)s] %(name)s: %(message)s"
heartbeat:
intervalSecs: 5
measures: { cpu: true, memory: true, disk: false }
tags: {}
metricEmission:
target: "log"
targetConfig: { logFileName: "/greengrass/v2/logs/{ComponentFullName}.metric.log" }
component:
global:
defaults: { pollIntervalMs: 1000, publishMode: "onChange", maxGap: 8 }
instances:
- id: "plc1"
connection: { transport: "tcp", host: "10.0.0.50", port: 502, unitId: 1, timeoutMs: 1000 }
publish: { batchMs: 0 }
write: { enabled: true }
pollGroups:
- id: "main"
pollIntervalMs: 1000
signals:
- { name: "Counter16", table: "holding", address: 0, type: "uint16" }
- { name: "Scaled", table: "holding", address: 40, type: "uint16", scale: 0.1 }

What changes vs the other platforms

Option Effect
--platform GREENGRASS (in the recipe Run) Selects IPC messaging and GG_CONFIG as the config source; publishes route through the Nucleus rather than a broker. The recipe’s accessControl grants pub/sub on IPC and IoT Core.
heartbeat.* Standard edgecommons heartbeat — the UNS state keepalive (ecv1/{device}/modbus-adapter/state) plus CPU/memory/disk sys measures. Independent of Modbus polling; destination (default local) is the local channel on GG IPC.
metricEmission.target: log Routes southbound_health and the Modbus operational metrics to a rotating log file (vs messaging/cloudwatch/prometheus). {ComponentFullName} resolves to the deployed component name.
signal scale Scaled publishes raw × 0.1 (raw 12312.3); a scaled integer is emitted as a float.

On startup each instance’s connect() blocks and retries every 5 s until the device answers, so a device down at deploy time does not crash the component — it logs and keeps trying, and the instance becomes ready once connected.


On Kubernetes the config is mounted as a directory (the whole ConfigMap volume) at /etc/edgecommons; the CONFIGMAP source watches the kubelet ..data symlink swap and hot-reloads in process on kubectl apply. With --platform auto, the library detects KUBERNETES from the ServiceAccount token, picks the CONFIGMAP source and MQTT transport (broker from the config), and takes identity from the Downward API — so the container needs no CLI args.

k8s/configmap.yaml:

apiVersion: v1
kind: ConfigMap
metadata:
name: modbus-adapter-config
data:
config.json: |-
{
"logging": { "level": "INFO" },
"messaging": {
"local": { "type": "mqtt", "host": "emqx.default.svc.cluster.local", "port": 1883, "clientId": "modbus-adapter" }
},
"metricEmission": { "target": "prometheus", "targetConfig": { "port": 9090, "path": "/metrics" } },
"component": {
"global": { "defaults": { "pollIntervalMs": 1000, "publishMode": "onChange", "maxGap": 8 } },
"instances": [
{
"id": "plc1",
"connection": { "transport": "tcp", "host": "modbus-sim.default.svc.cluster.local", "port": 5020, "unitId": 1, "timeoutMs": 1000 },
"publish": { "batchMs": 0 },
"writes": { "allow": [] },
"pollGroups": [
{ "id": "main", "pollIntervalMs": 1000,
"signals": [
{ "name": "Counter16", "table": "holding", "address": 0, "type": "uint16" },
{ "name": "Scaled", "table": "holding", "address": 40, "type": "uint16", "scale": 0.1 }
] }
]
}
]
}
}

What changes vs the other platforms

Aspect Effect
Config source CONFIGMAP Reads config.json from the mounted ConfigMap directory and hot-reloads when you kubectl apply a new ConfigMap (the ..data swap) — no pod restart.
messaging.local.host Point at an in-cluster broker Service DNS name (emqx.default.svc.cluster.local).
connection.host Point at the device/gateway’s Service or reachable address — the adapter runs in-cluster, so the device must be reachable from the pod network.
Identity (no -t) The Thing name resolves from the Downward API (EDGECOMMONS_THING_NAMEPOD_NAME), so the {device} token of every UNS topic is the pod name unless overridden.
metricEmission.target: prometheus Exposes southbound_health and the Modbus operational metrics as OpenMetrics text at :9090/metrics for scraping (the default metric target on KUBERNETES).
Health/probes The Deployment exposes the library’s HTTP health endpoint (/startupz, /livez, /readyz) for k8s probes.

Polling, type, deadband, and command behavior are identical to the other platforms — only the config source, broker/device addressing, identity, and metric target differ.


How the cross-cutting options affect runtime

Section titled “How the cross-cutting options affect runtime”

These behaviors apply to every configuration above.

The poll manager turns each group’s signals into the fewest Modbus reads possible: signals on the same table are sorted by address and merged into contiguous read blocks, bridging gaps up to maxGap and capping each block at the protocol limit (125 holding/input registers, 2000 coil/discrete bits). Net bus load ≈ (read blocks per group) × (1000 / pollIntervalMs) requests/second per group. Two levers:

  • Lower pollIntervalMs → fresher data, proportionally more requests and messages.
  • Raise maxGap → nearby signals collapse into one larger read (fewer round-trips, lower per-request overhead) at the cost of reading some unused registers in between. Coalescing is per table, so mixing tables in a group means at least one read per table.

A poll-group thread measures its own work time and waits pollIntervalMs − elapsed, so a slow read shortens (never lengthens) the next sleep — the configured cadence is the ceiling, not an addition.

Decoding raw registers (type / wordOrder / byteOrder / scale / bit)

Section titled “Decoding raw registers (type / wordOrder / byteOrder / scale / bit)”

Modbus carries only bits and 16-bit registers; richer types are synthesized in codec.py. A read block’s registers are sliced per signal, then assembled: wordOrder orders the registers (big = most-significant first; little = reversed), byteOrder orders the bytes within each register, and the type’s width decides how many registers are consumed. scale/offset then apply the linear transform; bit extracts a single bit. If a decode raises (e.g. a malformed string), that signal is published with quality BAD and the rest of the block continues.

Deadband and publish mode (data freshness vs message volume)

Section titled “Deadband and publish mode (data freshness vs message volume)”

Under publishMode: onChange, every decoded value is compared to the last published value via the signal’s deadband and only republished if it passes — the first reading after start always publishes. This suppresses noise/jitter so steady signals don’t flood the bus. publishMode: always bypasses the deadband and publishes every poll. batchMs is orthogonal: it coalesces whatever was published in a window into fewer messages.

UNS addressing, sanitization, and precedence

Section titled “UNS addressing, sanitization, and precedence”

A data topic is ecv1/{device}/modbus-adapter/{instance}/data/{signal}, minted and validated by the library’s UNS builder — {device} is the resolved thing name (last hierarchy level), {instance} the device instance id, and {signal} the signal name passed through the UNS token sanitizer (/, +, #, \, control chars → _; .. rejected) so a channel token can never inject a level or a wildcard. There are no config topic templates. topic.includeRoot optionally inserts the site level after ecv1 on a multi-site broker. Timing/coalescing keys (pollIntervalMs, publishMode, maxGap) resolve group ▸ instance defaultsglobal.defaults ▸ built-in; batchMs resolves from publish ▸ instance/global defaults.

At startup each instance’s connect() blocks and retries every 5 seconds until the device answers, so a device down at launch doesn’t crash the adapter — other instances keep running (each instance has its own worker/connection). connection.timeoutMs bounds each individual request; a read that times out, errors, or returns a Modbus exception marks every signal in that read block with quality BAD (value null) and increments the readErrors counter, while the loop stays alive and retries on the next interval. The southbound_health metric’s connectionState (1/0) and readErrors reflect this; the richer ModbusConnection and ModbusPoll metric families add attempt/drop/read-block counters. Metrics are emitted to metricEmission.target (auto-routing to the UNS metric class under messaging) and the compatibility counters remain queryable via the sb/status command verb. A link up/down transition also raises/clears a critical alarm on evt/critical/connection immediately (the same channel for the drop and the restore, so a console tracking evt/critical/# sees both ends). Each instance’s current up/down state is additionally surfaced per-slave in the main state keepalive’s instances[] array ({instance, connected, state, detail}), driven by the same live poll reads (not a cached client flag), so a mid-session loss reads connected: false promptly.

Polling is the read plane. The command surface is separate — served by the library command inbox (ecv1/{device}/modbus-adapter[/{instance}]/cmd/{verb}), with the target device selected by the topic’s instance token or an instance field in the request body. Every reply is { "ok": true, "result": … } or { "ok": false, "error": … }.

  • Writes (sb/write) accept a signal only when its stable signal.id is on the instance’s writes.allow list, checked before any device I/O; a wholly-refused batch replies WRITE_NOT_ALLOWED. { "writes": [ { "name": "Setpoint", "value": 42.5 } ] } (or a single { "name": …, "value": … }). Only writable tables accept writes — coil (FC5/FC15) and holding (FC6/FC16); discrete/input and bit (single-bit) writes are reported per-entry as ok:false. scale/offset are inverted on the way down. Each attempted write also emits an evt/info/write (success) or evt/warning/write (failure) audit event.
  • Reads (sb/read) are request/reply and return { id, reads: [...] } — on-demand, independent of the poll loop.
  • Control verbs sb/status / sb/signals return instance state (the keepalive’s state token, plus connected/paused) + counters and the full signal list; sb/browse pages that inventory; sb/pause / sb/resume suspend and resume the instance; reconnect re-establishes the link and repoll forces an immediate poll (refused while paused).

A signal-ref in any command is either { "name": "<configured signal>" } or an explicit { unitId?, table, address, type, wordOrder?, scale?, … } for arbitrary access. See reference/messaging-interface.md for the full payloads.